Your technology partner
with innovative products
and affordable prices !

DATAKOM DFC-0108 power factor controller (8 steps) 96x96mm

* All prices are retail and VAT exclusive

DATAKOM DFC-0108 allows the power factor of the installation to be stabilized to the requested value by switching capacitor banks and inductive reactors through contactors.
The unit allows the visualization of various AC parameters as a network analyzer. It makes harmonic analysis of voltages and currents up to the 31th component.
Stepping algorithms are selectable between various types.
Thanks to the automatic setup function, the commissioning and programming are made easy.
The optimal stepping program provides longest contactor and capacitor life cycles.
The unit fits into a standard 96x96mm panel opening.

FEATURES:
  • Small size
  • Cost effective and high performance
  • True RMS AC measurements, high accuracy
  • Easy commissioning through automatic setup
  • Automatic CT reverse polarity correction
  • Electronic/mechanical power counter selection
  • Supports single-phase and tri-phase banks
  • Per-phase regulation capability
  • Connection/disconnection of all banks at once
  • Adjustable delay timers
  • Per phase and total V-A-kW-kVAr-cos display
  • THD display of all V-I parameters (31 harmonic)
  • VT ratio for MV applications
  • kW and kVAr tick output possibility
  • Front panel programmable
  • Low panel depth, easy installation
  • Wide temperature range
  • Sealed front panel (IP54)
  • Plug-in connection system, easy replacement

TECHNICAL SPECIFICATIONS:
Power Supply Input: 170 - 275VAC, 50 - 60Hz nominal (± 10%) between L1-N
Measurement Input Range:
Voltage inputs: 10 - 300 V AC (L-N)
                             20 - 520 V AC (L-L)
Current inputs: 0.2 – 5.5 A AC
Frequency: 30 - 100 Hz
Accuracy:
- Voltage: 0.5%+1digit
- Current: 0.5%+1 digit
- Frequency: 0.5%+1 digit
- Power(kW,kVAr): 1.0%+2digit
- Power factor: 0.5%+1 digit
Measurement Range:
- CT range: 5/5A to 5000/5A
- VT range: 0.1/1 to 200.0/1
- kW range: 0.1 kW to 6.5 MW
Power Consumption: < 4 VA
Voltage burden: < 0.1VA per phase
Current burden: < 1VA per phase
Relay Outputs: 5A @ 250VAC
Operating Temperature: -20°C to +70°C (-4 to +158F).
Maximum humidity: 95% non-condensing.
Degree of Protection: IP 54 (Front Panel), IP 30 (Back panel)
Enclosure: Non-flammable, ROHS compliant, ABS/PC (UL94-V0)
Installation: Flush mounting with rear retaining brackets
Dimensions: 102x102x53mm (WxHxD)
Panel Cutout: 92x92mm
Weight: 370 gr
EU Directives Conformity:
- 2006/95/EC (low voltage)
- 2004/108/EC (EMC)
Norms of reference:
- EN 61010 (safety requirements)
- EN 61326 (EMC requirements)

WE DO NOT SHIP THIS PRODUCT TO USA AND CANADA


* All prices are retail and VAT exclusive